Iskra BR6 Overload Relay

The Iskra BR6 overload relay provides overload protection for electric motors with operational currents up to 14 A and operational voltages up to 690 V AC.

It has electrically isolated auxiliary contacts, a manual stop function marked “0” and a “Test” function for checking the control circuit.

Iskra BR6 overload relay

Setting ranges and maximum backup fuses

The gL/gG fuse ratings below provide the short-circuit protection specified in the source catalogue for the indicated coordination type. Select the overload setting for the motor and verify the complete starter and protective-device combination.

Setting range (A) Maximum gL/gG fuse (A), type 1 coordination Maximum gL/gG fuse (A), type 2 coordination
0.11–0.16 20 0.5
0.16–0.25 20 1
0.25–0.4 20 2
0.4–0.6 20 2
0.6–0.9 20 4
0.9–1.3 20 4
1.3–1.9 20 6
1.9–2.8 20 6
2.8–4 20 10
4–6 20 10
6–9 20 16
8–11 25 20
11–14 35 25

Technical data

Characteristic Value
Standards IEC/EN 60947-4-1, IEC 60947-5-1, UL 508
Weight 0.08 kg

Rated operational current Ie, AC-15

Voltage Normally open (NO) Normally closed (NC)
220/240 V 1.5 A 1.5 A
380/415 V 0.5 A 0.7 A
500 V 0.3 A 0.5 A

Rated operational current Ie, DC-13

Ratings for both auxiliary contacts.

Voltage Current
24 V 0.9 A
60 V 0.75 A
110 V 0.4 A
220 V 0.2 A

Back to Iskra overload relays

Contact Appel with the type designation and application details for product selection.