TF 142-1 AA 06

Illustration: TF 142-6 AC 06
Dimensional drawing: tf142 Circuit diagram: two changeover contacts Sensor shape a

Thermostat in an insulating enclosure (ABS) with 2 changeover contacts

No longer available

Part number 010526259
Upper switching point – 50 … – 10 °C
Adjustable switching differential, K 1.5 … 16
Lowest lower switching point – 56 °C
Maximum sensor temperature 150 °C
Factory setting – 18 … – 20 °C
Sensor charge and shape Vapour / A
Capillary tube length 2 metres
Weight approx. 0.8 kg
Permissible ambient temperature -50 …. +70°C
Degree of protection according to DIN 40 050/IEC 529 IP 55
Rated operational current AC1, 230 V 16A
Rated operational current AC1, 400 V 10A
Rated operational current AC15, 230 V 6A
  • Scale in °C and °F
  • Insulating enclosure (ABS)
  • Provision for 2 PG 13.5 cable glands